Vulcan vs BrandGuard vs O'Hagin vs Embers OutFour ember vents. Which one goes where?
A plain-English comparison of the ember-resistant vents sold in California, for Pasadena, Altadena and Los Angeles homeowners. How each one works, what independent lab tests found, what the code allows, and what installation costs.
Updated November 10, 2026. Maker descriptions are each maker's claims, not RF1 test results.
The short answer
There's no single best vent. It depends where it goes.
Vents sit in five main spots on a house, and each spot has a different best fix. Here's the quick version before the details.
- Roof
Low-profile roof vents with 1/8-inch metal mesh, like O'Hagin Fire & Ice, or a baffled ridge vent along the peak.
California's code lets roof vents use noncombustible mesh between 1/16 and 1/8 inch. In IBHS testing, wind-driven-rain ridge vents and off-ridge vents filled with steel wool did well.
- Gable ends
A purpose-built ember vent: baffle (BrandGuard), honeycomb (Vulcan) or multi-louver (Embers Out).
IBHS found gable vents especially easy for embers to get through, even with mesh, and wildfire-resistant gable vents did better than mesh alone.
- Eaves and soffits
A purpose-built ember vent sized for the eave, or 1/8-inch metal mesh behind your existing vent on an older home.
Boxed-in (soffited) eaves let fewer embers in than open eaves in IBHS testing.
- Foundation and crawlspace
A purpose-built ember vent, or 1/8-inch metal mesh on an older home, with nothing that burns in front of it.
These vents sit low and are among the most exposed, so keep the first 5 feet in front of them clear.
- Dryer and exhaust
A metal wall cap with a louver or flap that closes. Never mesh.
Lint clogs mesh. IBHS asks for a working flap instead, and a metal one for its higher Plus level.
Side by side
Vulcan, BrandGuard, O'Hagin and Embers Out, compared.
| Question | VulcanHoneycomb vent | BrandGuardBaffle vent | O'Hagin Fire & IceLow-profile roof vent | Embers OutMulti-louver vent |
|---|---|---|---|---|
| How it works | Aluminum honeycomb cells with a coating that swells shut in heat, plus a stainless steel mesh behind them. | Overlapping metal baffles make embers change direction, with a fine 1/16-inch stainless mesh behind them and a strip that swells in heat. | A low dome on the roof with 1/8-inch metal mesh and a stainless steel wire filament that catches embers. | Several metal louvers, or a metal micro filter, in a galvanized steel or aluminum frame. |
| Where it fits | Eave (round), soffit, foundation, gable, continuous, dormer, plus retrofit kits. | Soffit and eave, gable, continuous, foundation, dormer, balcony, garage and roof retrofit. | Roofs only: comp shingle, tile, slate, shake and metal. | Gable, soffit, frieze board and foundation, including drop-in retrofits. |
| Testing claim | Vulcan says it's tested to ASTM E2886 and has an ICC-ES evaluation report (ESL-1300). | BrandGuard says it's tested to ASTM E2886 and E2912. | O'Hagin says ridge and off-ridge roof vents can't be tested to ASTM E2886, so they meet the code through the roof-vent mesh path. | Check the exact model on the State Fire Marshal's listing before buying. |
| Independent lab results | NIST (2025): at heat far above the standard test, listed honeycomb vents let flames through, especially once the eave caught fire. | NIST (2025): at the same high heat, baffle designs held up better than honeycomb designs. Still not perfect. | No brand-specific test we could find. | No independent test data we could find. |
| Airflow | Less open area than plain mesh. Check the net free area on the spec sheet. | Less open area than plain mesh. Check the net free area on the spec sheet. | O'Hagin lists 64.8 sq in of open area per vent with 1/8-inch mesh, vs 72.0 with 1/4-inch. | Less open area than plain mesh. Check the net free area on the spec sheet. |
| Upkeep | Look once a year for debris, damage and paint over the cells. | Finer 1/16-inch mesh clogs faster, so clear debris once a year. | Look once a year for debris and damage in the mesh. | Look once a year for debris, damage and gaps around the frame. |
| Published price | Not published by Vulcan. | On BrandGuard's store (Oct 2026): eave $11 to $15, soffit $56 to $93, foundation $64 to $78, gable $94 to $399. | About $45 to $52 per vent at one retailer we checked. | Not published. |
Swipe the table sideways on a phone. Descriptions and testing claims are the makers'; lab results are from NIST. Listings change, so confirm the exact model on the State Fire Marshal's Building Materials Listing (vents are category 8165) before you buy. Plain 1/8-inch metal mesh, the cheapest option, has its own page.
What the tests found
No vent is fireproof. Some hold up better.
NIST, 2011
Embers didn't go out when they landed on vent mesh. They kept burning until they were small enough to fit through, down to about 1 mm. That's why the size of the openings matters so much.
IBHS, 2017
1/4-inch mesh should not be used on any vent. 1/8 or 1/16 inch is better, though 1/16 needs more cleaning. Gable vents were especially vulnerable even with mesh, and ember-resistant gable vents did better than mesh alone.
NIST, 2025
NIST tested listed vents at heat roughly five to eight times the standard test. Baffle vents held up better than honeycomb vents. Some honeycomb vents that pass the standard test let flames through, especially once the eave itself caught fire.
IBHS, after the 2025 LA fires
In an early report on 247 homes, only 7.8% had proper fire-safe vents with 1/8-inch or finer metal mesh.
California fire losses, 2013 to 2018
A study of CAL FIRE damage inspections found vent screens among the most consistently important features in whether a home survived.
What this means: a listed ember vent is a big step up from old 1/4-inch screen, but it's one layer. Vents work best with a clear Zone 0, sealed gaps around each vent and nothing stored against the house.
Mesh or a new vent
What California's code actually allows.
Building new or rebuilding in a fire hazard zone. Since January 1, 2026, California's Wildland-Urban Interface Code (Section 504.10) says wall, eave, gable and foundation vents must be listed by the State Fire Marshal or tested to ASTM E2886. Mesh between 1/16 and 1/8 inch only qualifies for roof vents, like dormer and ridge vents. Gable and dormer vents also need to sit at least 10 feet from property lines.
Living in an existing home. No state rule makes you replace your vents. Fitting 1/8-inch noncombustible metal mesh behind the vents you have is the cheapest upgrade, and IBHS accepts it. Never use plastic or fiberglass screen, since it melts.
Remodeling or adding on. Whether a remodel triggers the new vent rules can depend on your city or county, so ask your building department before you start.
What counts
What insurers, IBHS and AB 38 look for.
- IBHS Wildfire Prepared Home
- Accepts either vents tested to ASTM E2886, with the joints sealed per the maker's instructions, or noncombustible, corrosion-resistant mesh with openings no bigger than 1/8 inch. Dryer vents need a working louver or flap, and a metal one for Plus.
- Insurance discounts (Safer from Wildfires)
- California's regulation lists fire-resistant vents as a discount item and points to listed vents. The Department of Insurance's consumer page mentions 1/16 to 1/8-inch metal mesh. Those don't fully match, so ask your insurer what proof they accept before you buy.
- AB 38, when you sell
- Sellers of homes built before 2010 in High or Very High fire hazard zones must disclose vents with openings over 1/8 inch or that aren't flame and ember resistant. It's a disclosure, not an order to replace them.
Cost estimator
What would your vents cost to replace?
Walk around the house and count each kind. The numbers come from a 2024 California study by Headwaters Economics and fire scientist Stephen Quarles, funded by CAL FIRE. Installed cost depends more on where a vent sits than on the brand.
Your rough installed cost
$0
0 vents
The low end is the 2024 Headwaters Economics study figure for each vent (2023 prices). The high end adds 20% for price changes since then and Southern California differences; the study says SoCal usually runs within 10% of its numbers. Sealing gaps around each vent adds a few dollars per foot.
This is a benchmark, not a quote. RF1's price can be higher or lower depending on access, roof type and which fix each vent needs.
Get every vent counted, freeQuestions
Ember vent questions, answered straight.
There isn't one best vent for every opening. In NIST's 2025 high-heat tests, baffle vents like BrandGuard held up better than honeycomb vents like Vulcan. On the roof, low-profile vents with 1/8-inch metal mesh, like O'Hagin Fire & Ice, are the usual choice, and the code allows mesh there. On an existing home, 1/8-inch metal mesh behind the vents you have is the cheapest upgrade. Whatever you buy, check the exact model on the State Fire Marshal's Building Materials Listing first.
Keep reading
- Metal mesh retrofitPhifer EmberScreen, BrandGuard ember-resistant mesh
- Baffle ventsBrandGuard Vents
- Honeycomb ventsVulcan Vents
- Multi-louver ventsEmbers Out
- Low-profile roof ventsO'Hagin Fire & Ice
- Exhaust wall capsAble FireShield
- Vent calculatorHow many vents your attic or crawlspace needs, by brand
- Home hardening in Los AngelesVents, Zone 0, gutters and gaps, in order
Sources
- 2025 California WUI Code 504.10 (Town of Paradise summary)
- NIST Technical Note 2341 (2025), vent performance at high exposure
- NIST, Manzello et al., embers and building vents (2011)
- IBHS, Vulnerability of Vents to Wind-Blown Embers (2017)
- IBHS findings on the Palisades and Eaton fires
- Report on IBHS's early LA findings (7.8% of homes with fire-safe vents)
- Syphard and Keeley (2019), factors in California home losses
- IBHS Wildfire Prepared Home 2025 Technical Standard
- California Department of Insurance, Safer from Wildfires
- California Civil Code 1102.6f (AB 38 disclosure)
- Headwaters Economics and Quarles, Retrofitting a Home for Wildfire Resistance (2024)
- UC ANR Fire Network, Vents
- Fire Safe Marin, Vents FAQs
- Vulcan Vents
- ICC-ES ESL-1300 (Vulcan)
- BrandGuard Vents
- BrandGuard retail store
- O'Hagin California vent compliance bulletin (2026)
- Embers Out
- State Fire Marshal Building Materials Listing (vents, category 8165)
Facts checked October 30, 2026. Prices checked October 2026.

Don't wait for the next red flag day. Start with one call.
A free assessment, a plan with prices, and one team to do the work. Pasadena, Altadena and across Southern California.